SPECIFICATIONS
ELECTRIC

MODEL
DDH-3000
Compact


MODEL
DH-3000

MODEL
DH-5000

MODEL
DH-5500

MODEL
DH-12000

MODEL
DH-20000
CFM (Cubic Feet Per Minute)
3000
3000
5000
5500
12000
20000
VOLTS
460
460
460
480
480
460
PHASE
3
3
3
3
3
3
HERTZ
60
60
60
60
60
60
Full Load Amps (Electric)
68
90
140
165
350
 
Heater Kilowatts
N/A
64 KW
100 KW
120 KW
250 KW
 
BTU's Per Hour
N/A
220,000
341,000
400,000
850,000
1,500,000
STATIC PRESSURE
2.5" WG
1.5" WC
1.5" WC
1.5" WC
2.5" WC
 
DUCT INLET SIZE
18"
18"
18"
18"
18" (qty 2)
20" (qty 3)
DUCT OUTLET SIZE
18"
18"
18"
18"
18" (qty 2)
20" (qty 3)
LENGTH
7 ft 4 in*
11 ft 3 in
14 ft
14 ft 9 in
16 ft
22 ft
WIDTH
2 ft 10.5 in*
4 ft
4 ft
5 ft
6 ft
5 ft
HEIGHT
4 ft 8 in*
4 ft 10 in
5 ft 6 in
5 ft 6 in
8 ft
9.8 ft
WEIGHT
1,200 lbs**
3,500 lbs
3,800 lbs
3,500 lbs
7,300 lbs
10,500 lbs
Generator Size Required
65 KW
75 KW
125 KW
150 KW
250 KW
 
Desiccant Media Type
Silica Gel
Silica Gel
Silica Gel
Silica Gel
Silica Gel
Silica Gel
Desiccant Wheel Diameter
--
30"
38"
42"
60"
 
Process Motor HP / RPM
--
5.0 / 3600
7.5 / 3600
7.5 / 1800
20 / 1800
20
Reactivation Motor HP / RPM
--
1.5 / 3500
2.0 / 3500
2.0 / 3600
4.5 / 3500
7.5 / 4000
* Measurements include casters attached.
** weight is estimated at this time.


GAS REACTIVATION SPECS

MODEL
DH-3000
MODEL
DH-5000
MODEL
DH-5500
MODEL
DH-12000
MODEL
DH-20000
Natural / Propane YES YES YES YES YES
Full Load Amps (Gas) 25 25 25 40 39
Gas Consumption 3 GPH 3.5 GPH 7-10 GPH 7-10 GPH  
BTU's Per Hour 253,000 341,000 400,000 1,000,000 1,500,000
Max. Inlet Pressure (PSI) 1/2 PSI 1/2 PSI 1/2 PSI 1/2 PSI  
Max. Inlet Pressure (W.C.) 7"-14" WC 7"-14" WC 7"-14" WC 7"-14" WC 7"-15" WC
Regulator Required At Inlet  w/propane w/propane      
Operating Pressure 2" WC 2" WC 2" WC 2" WC 2" WC
Generator Required 20 KW 20 KW 60 KW 75 KW  

 